I. product overview
The y-type filter can effectively remove the mechanical impurities in the pipeline fluid, which can be used to filter the liquid that has no corrosive effect on stainless steel or cast iron.
2. Use the occasion
Suitable for circulating cooling water system, heat exchange system, air conditioning and refrigeration system, central heating system, hot water boiler system, etc., applicable industries including construction, chemical industry, electric power, metallurgy, rubber, paper making, textile, coal, food and other industries. Filter requirements through the medium temperature of the water treatment instrument shall not exceed 225 ℃;
Third, product characteristics
1. Simple structure and strong reliability;
It is convenient to remove, clean and maintain.
3. Filter screen specifications, and meet different requirements of filtering;
4. Low price and long service life.
Iv. Product model description
The equipment has 14 kinds of specifications, such as DN50mm ~ DN600mm, according to the nominal diameter of the water outlet. Nominal pressure is 1.6mpa; The structure is divided into two types: Y and T.
5. Structure and dimensions
This product consists mainly of import and export flanges, shells, filter parts and flange covers, and its basic structure and contour size are shown. Remove the flanges, remove the filter and remove the trapped impurities from the filter.
Technical performance parameters
Nominal pressure: 1.6 MPa (other specifications can be special);
Working temperature: 225 ℃ or less;
Screen specification: 10 ~ 120 mesh/inch optional, the default specification is 20.
7. Installation and use
1. Attention should be paid to the direction of the arrow in the shell (horizontal or downward) in the direction of the flow direction of the medium and to keep the flange cover down so that it can discharge when opening.
2. It is recommended to set the bypass so as to not affect the normal operation of the system when cleaning or failure of the filter;
3. There should be a certain distance between the filter and the actuator or instrument, generally 6 ~ 10 times as much as the nominal diameter;
4. When used with water treatment equipment, the filter shall be installed before the inlet of the water treatment equipment;
5. The filter parts shall be cleaned regularly, and the cleaning cycle and cleaning agent shall be determined by the user according to the conditions of use.